|

Propane Furnaces
Overview:
Furnaces in an RV aren't all that different than a gas-fired forced air furnace in a residential application. They use 12 volt
power to run the blower and provide ignition rather than 120 volts, but the principle is the same. They burn gas in a combustion chamber which
gives off heat. This heat is then blown through the duct work by a blower fan and cooler air is returned to the furnace via a cold air return
duct. RV furnaces do have "chimneys" of sorts, but it's just a stainless steel vent cover on the side of the RV where the hot exhaust
gasses escape.
The propane furnace has a number of safety features built in. The electronic ignition will spark at the appropriate time to ignite
the gas and begin combustion. If there is not adequate combustion airflow through the burner a sail switch will sense this and shut down the
furnace to prevent overheating of the combustion chamber in the event the intake air is clogged or restricted by mud dauber nests or whatever else
"built" a home in there. If the combustion chamber gets too hot, a high limit switch will shut down the burner until it cools. And, of
course, the furnace only runs in response to a request for heat from the RV's thermostat. The fan blower is not controlled by the thermostat. The
fan will start once the heat exchanger has warmed up a bit in order to not blow cold air on you at first. Later, when the burner has stopped, the
fan will continue to run until the heat exchanger cools down.
Propane furnaces are found underneath the floor in the RV, generally in a non-storage basement area. The ductwork from these furnaces
runs up into the coach and outlets either in the floor, very low along interior walls, or a combination of both. Propane furnaces also provide
basement heat to keep the holding tanks and water lines from freezing. Air conditioning and heat pump units are found on the roof and use a separate
ductwork system. These ducts are found in the roof of the RV and do not feed the basement storage area therefore running the heat pumps to keep the
water system from freezing is a fruitless effort. You must run the furnace to prevent the water system from freezing.
Most RVs now use a common thermostat for both heating and cooling. This thermostat can control both the LP furnace as well as the air
conditioning and heat pumps (sometimes referred to as "electric heat"). Many do have interlocks on them so that you can't run one heat pump
and one furnace but there are lots of variations on this so, like they say, "your mileage may vary". Most thermostats will automatically kick
in the propane furnace when you select heat pumps if the temperature differential between the thermostat set point and the actual interior temperature
is greater than 5 degrees. Once you reach the set point, the furnace will stop and the heat pumps will take over the rest of the heating tasks. If it's
too cold, and the heat pumps can't handle it, the furnace will kick in again if the 5 degree differential reappears.
Troubleshooting:
|
BURNER FAILS TO IGNITE AND BLOWER FAILS TO RUN
|
|
Condition
|
Solution
|
|
No Electrical Power to the furnace
|
Reconnect or replace power source
|
|
Thermostat defective
|
Replace thermostat
|
|
Thermostat wires broken or shorted
|
Replace wire or wires
|
|
Circuit breaker defective or tripped
|
Reset circuit breaker and check amp draw from motor according to furnace's specifications
|
|
Blower relay defective
|
Replace relay
|
|
Wire off motor or relay
|
Reconnect wire
|
|
Bad ground
|
Clean and secure grounds
|
|
Blower motor defective
|
Replace motor
|
|
BURNER RUNS BUT FAILS TO IGNITE
|
|
Low voltage
|
Correct Power Supply
|
|
Gas pressure incorrect
|
Set pressure to minimum of 11" W.C. with all appliances running. Replace regulator if not obtainable.
|
|
Furnace ground wires not secure
|
Clean and secure grounds
|
|
Air intake restricted
|
Clean air intake
|
|
Motor running slow
|
Correct polarity
|
|
Combustion air wheel loose
|
Check voltage, if 12 VDC while running, replace motor
|
|
Exhaust blocked
|
Clean exhaust
|
|
Sail switch defective
|
Reposition and tighten
|
|
Limit switch defective
|
Replace switch
|
|
Edge connector on circuit board dirty
|
Clean with pencil eraser
|
|
Circuit board defective
|
Clean plug contacts. If still defective, replace (check on board tester when possible)
|
|
Gas valve defective
|
Replace valve or valve coil
|
|
Main burner orifice blocked
|
Clean main burner orifice or replace
|
|
High tension lead wire defective
|
Replace wire
|
|
Electrode out of adjustment
|
Adjust electrode (don't crack the porcelain)
|
|
Electrode defective or cracked
|
Replace electrode
|
|
Obstructed burner head
|
Clean burner head
|
|
BURNER IGNITES BUT IGNITION SYSTEM "LOCKS OUT" AND TURNS BURNER OFF
|
|
Low gas pressure
|
Set pressure to minimum of 11" W.C. with all appliances running. Replace regulator if not obtainable
|
|
Exhaust blocked
|
Clean exhaust
|
|
Combustion air loose
|
Reposition wheel and tighten
|
|
Electrodes out of adjustment
|
Adjust electrodes to proper specs
|
|
Electrode defective
|
Replace electrode
|
|
Circuit board defective
|
Clean plug contacts. If still defective, replace.
|
|
Flame sensor wire between electrode and circuit board defective
|
Replace wire
|
|
Air leakage at gaskets
|
Replace gasket
|
|
Defective heat exchanger
|
Replace heat exchanger
|
|
SOOTING (caused by lazy yellow flame)
|
|
Low gas pressure
|
Set pressure to minimum of 11" W.C. with all apliances running. Replace regulator if not obtainable
|
|
Low voltage
|
Correct power supply
|
|
Air leakage at gaskets
|
Replace gaskets
|
|
Combustion wheel installed backwards
|
Reposition wheel and tighten
|
|
Blockage in heat exchanger or burner head
|
Clean or replace
|
|
Faulty motor
|
Replace motor
|
|
FAN RUNS CONTINUOUSLY WITH THERMOSTAT "OFF"
|
|
Defective thermostat
|
Replace thermostat
|
|
Shorted thermostat leads
|
Replace wiring
|
|
Defective relay
|
Replace relay
|
|
LIMITING = BURNER CYCLING ON AND OFF BLOWER RUNS CONSTANTLY WITH THERMOSTAT ON
|
|
Furnace over fired
|
Set gas pressure to a minimum of 11" W.C. with all appliances running. Replace regulator if not obtainable. Also, check main
burner orifice, it must comply with the furnace's specifications.
|
|
Restricted return air supply
|
Make sure return air meets furnace's minimum requirements
|
|
Restricted or insufficient discharge ducting
|
A) Ducting must meet minimum specifications
B) No excess ducting or unnecessary bends
C) All closeable registers must be fully open and unrestricted
|
|
Defective limit switch
|
Replace limit switch
|
|
BLOWER SHUTS OFF AT SAME TIME BURNER SHUTS OFF
|
|
Wired wrong
|
Correct wiring
|
|
Faulty relay
|
Replace relay
|
|
BLOWER VIBRATES OR IS NOISY
|
|
Motor mount loose
|
Tighten motor mounting bracket
|
|
Damaged blower wheel
|
Replace blower wheel
|
|
Motor shaft bent
|
Replace blower motor
|
|
INSUFFICIENT HEAT
|
|
Furnace under fired
|
A) Set gas pressure to 11" W.C. with all appliances running. Replace regulator if not obtainable.
B) Check burner orifice. It must comply with furnace's specifications.
C) Check ducting and return air according to furnace's specifications.
|
Submitted by Mark Quasius and Mike Sundberg - 3/18/06
Click Your browser's "Back" button to return to the previous page
or chose another category from the side menu.
|